OTI DALI 25/220-240/300 D NFC F L - 6977770436787O
Electrical data
Nominal input voltage 220…240 V
Mains frequency 0/50/60 Hz
Input voltage AC 198…264 V
Input voltage DC 176…276 V
Current set DALI / NFC
Total harmonic distortion 9.50 %
Power factor λ > 0.95
ECG efficiency up to 90.5 %
Device power loss 2.0 W
Power loss in stand-by mode <0.15 W
Protective conductor current <0.5 mA
Inrush current 21 A
Max. ECG no. on circuit breaker 10 A (B) 17
Max. ECG no. on circuit breaker 16 A (B) 28
Max. ECG no. on circuit breaker 25 A (B) -
Surge capability (L/N-Ground) 2 kV
Surge capability (L-N) 1 kV
Nominal output voltage 54…240 V
U-OUT (working voltage) 54…240 V
Nominal output current 35…300 mA
Default output current 35 mA
Output current tolerance ±3 %
Output ripple current (100 Hz) < 1 %
Nominal output power 25 W
Galvanic isolation Non isolated